GD10P

Tecnology

Infrared

Measured gas

Acetaldehyde – C2H4O, Acetic acid – C2H4O2, Acetone / Propionaldehyde – C3H6O, Acetylene – C2H2, Benzene – C6H6, Butane – C4H10, Carbon Dioxide – CO2, Carbon disulfide – CS2, Carbonyl sulfide – COS, Chloroform – CHCl3, Cycloheptatriene – C7H8, Dichloromethane – CH2CL2, Dimethylbutane – C6H14, Ethane – C2H6, Ethanol – C2H6O, Ethylene – C2H4, Fluoromethane – CH3F, Hexane – C6H14, IC4 – IC4, IC5 – IC5, Isobutanol – C4H10O, Methane – CH4, Methanol – CH3OH, Methanol – CH4O, Methyl iodide – CH3I, Octane – C8H18, Pentane – C5H12, Phosgene – CCl2O, Propane – C3H8, Propanol – C3H7OH, Propylene – C3H6, Styrene – C8H8, Tetrachloroethylene – C2Cl4, Tetrafluoroethylene – C2F4, Tetrafluoromethane – CF4, Total HydroCarbons – THC, Trichloroethylene – C2HCl3, Xylene – C8H10

Manufacturer

Simtronics

  • Description

Description

Our ultimate Infra-Red point detector with versions covering a wide range of combustible gases.

Features
Life-time stability

The SimSource infrared light source is a solid-state component with a stable output and 60 years of expected lifteime. This, together with the Simtronics IR-path design gives you a detector with unparallelled stability.

No false alarms

Unlike most gas detectors in use today, the GD10P will give an error signal and not cause gas alarms in case of detector failure.

No poisioning or saturation
  • Immune to silicon vapours, H2S and other widely used agents.
  • High gas concentrations will not saturate the detector.
  • Can be used to detect gases where oxygen is not present, e.g. in sub-sea production units
Specification
General
Detection methodIR-absorbtion, dual wavelength, dual path
IR-SourceSolid state IR source, 50Hz flash
Gases detectedHydrocarbons, see separate data sheet for CO2 detection
Self-testContinuous
CalibrationFactory set, no field recalibration
Performance
Lifetime stability±5% of full scale (FS) reading
Accuracy±3% FS between 0-50 % reading
±5% FS between 50-100 % reading
Response timeT20 = 1 sec. (Option 0.3 sec)
T50 = 2.5 sec. (Option 0.7 sec)
T90 = 6 sec. (Option 1.6 sec)
Start-up timeLess than 60 sec.
Output Signal
StandardCurrent source 4 – 20 mA, max. load impedance 500 Ohm
OptionCurrent sink 4 – 20 mA
OptionHART®
Detector warnings:
Early clean opticsPre warning (1 mA pulse)
Clean opticsDirt accumulation (1 mA)
Clean opticsDirt accumulation (1 mA)
Option: Dirt accumulation (2mA)
Detector failureInternal fault (0 mA)
Electrial
Power supply24 V DC, range18-32 V DC
Power consumptionApprox. 3.5 W
Connection3 wires (0.5mm2 – 1.5mm2)
Cable entryM20 EExe cable gland
Temperature Range
Storage-40°C to + 70°C (-40°F to +158°F)
Operating-40°C to + 65°C (-40°F to +149°F)
Humidity (operation)100% RH
Exsplosion Proof Housing
Main housingEExd IIC T6
Terminal compartmentEExe
Protection categoryIP66/IP67 DIN 40050
Housing materialStainless steel SIS2343 (ASTM 316)