GD10PE – IR extended point Gas detector

Tecnology

Gas Chromatograph

Measured gas

Acetaldehyde – C2H4O, Acetic acid – C2H4O2, Acetone / Propionaldehyde – C3H6O, Acetylene – C2H2, Benzene – C6H6, Butane – C4H10, Carbon Dioxide – CO2, Carbonyl sulfide – COS, Chloroform – CHCl3, Cycloheptatriene – C7H8, Dichloromethane – CH2CL2, Dimethylbutane – C6H14, Ethane – C2H6, Ethanol – C2H6O, Hexane – C6H14, IC4 – IC4, IC5 – IC5, Isobutanol – C4H10O, Methane – CH4, Methanol – CH3OH, Methanol – CH4O, Methyl iodide – CH3I, Octane – C8H18, Pentane – C5H12, Phosgene – CCl2O, Propane – C3H8, Propanol – C3H7OH, Propylene – C3H6, Styrene – C8H8, Tetrachloroethylene – C2Cl4, Tetrafluoroethylene – C2F4, Tetrafluoromethane – CF4, Total HydroCarbons – THC, Trichloroethylene – C2HCl3, Xylene – C8H10

Manufacturer

Simtronics

  • Description

Description

GD10PE – IR extended point Gas detector

GD10PE is the solution for ducts where conventional line detectors does not fit properly and standard point detectors are too slow. GD10PE is designed to meet the evolving safety norms for gas turbines, but is equally suited for HVAC and other applications where fast, low level and reliable detection is required.

Features
High sensitivity, fast response

GD10PE has both, and is still protected against false alarms.

Life-time stability

The SimSource infrared light source is a solid-state component with a stable output and 60years of expected lifteime. This, together with the Simrad Optonics IR-path design gives you a detector with unparallelled stability.

No poisioning or saturation
  • Immune to silicon vapours, H2S and other widely used agents.
  • High gas concentrations will not saturate the detector.
  • Can be used to detect gases where oxygen is not present, e.g. in sub-sea production units
Low maintenance costs

GD10PE requires no regular field maintenance, apart from cleaning the optics. It has a fixed factory calibration, and is not recalibrated during its lifetime.

SAFE
Application
Offshore platforms

Protection of all kinds of air intakes (HVAC)

Chemical industry

High sensitivity gas monitoring

Gas turbines

Monitoring of ventilation air

Specification
General
Detection methodIR-absorption, dual wavelength, dual path
IR-SourceSolid state IR source, 50 Hz flash
Detection range0-20% LEL (0-1% Vol.) methane
Gases detectedHydrocarbons
Self-testContinuous
CalibrationFactory set, no field recalibration
Start-up timeLess than 60 sec.
Performance
Lifetime stability±1.4%LEL
Accuracy±1%LEL (0-10 % LEL reading)
±1.4%LEL (10-20 %LEL reading)
Response time
Detector reading:20%LEL test gas:
4% LEL1 sec.
10%LEL2.5 sec
18%LEL6 sec.
Output signal
StandardCurrent source 4 – 20 mA, max. load impedance 500 Ohm
OptionCurrent sink 4 – 20 mA
OptionHART®
Electrical
Power supply24 V DC, range18-32 V DC
Power consumptionApprox. 3.5 W
Connection3 wires (0.5mm2 – 1.5mm2)*(12 AWG – 22 AWG)
Cable entryM20 EExe cable gland
Temperature range
Storage-40°C to 70°C (-40°F to 140°F)
Operating-40°C to 65°C (-40°F to 158°F)
Probe, inside ductup to +85°C (185°F)
Humidity (operation)100% RH
Explosion proof housing
Main compartmentEExd IIC T6
Terminal comp.EExe
Protection categoryIP66/IP67 DIN 40050
Housing materialStainless steel SIS2343 (ASTM 316)
Dimensions104W x 105D (mm); *30.9 x 4.1 x 4.1 (inches) Overall
WeightApprox. 6.5 kg (14.3 lbs)
Approvals
ATEXDirective 94/9/EC, EMC directive 89/336/EEC Article 4
SILQualified for SIL2 and SIL3 systems

 